Flat cells (pre-filters) |
|
numerous measures to fit the specific housing |
|
efficiency classes from G2 to G4 (EN 779) |
|
frames in galvanized metal, plastic or reinforced carton |
|
filter media: progressive density glass fibres, synthetic fibres, foamed PUR, mesh of multilayer-alluminium, metal or stainless steel |
|
protective grids on both sides |
|
Pleated cells (pre-filters) |
|
numerous measures to fit the specific housing |
|
efficiency classes from G3 to F5 (EN 779) |
|
frames in galvanized metal |
|
filter media synthetic fibres |
|
protective grids (galvanized electrically welded steel wire) on both sides, variable square measures as to air flow velocity |
|
|
|
|

 |
Smooth pocket filters
|
numerous measures to fit the specific housing |
|
efficiency classes from G3 to F9 (EN 779) |
|
frames in galvanized metal |
|
filter media: |
-
|
fire resistant synthetic fibres (class F1 - DIN 53438) |
- |
glass microfibre mat |
Technical caracteristics: |
|
dP variable (as to efficiency class and measures) |
|
dP max. 800 Pa (synthetic fibres) - 600 Pa (glass mircofibre mat) |
|
temperature 90°C |
|
humidity 100% |
Upon request: |
|
plastic frame |
|
|
|
 |
Rigid pocket filters
|
measures 288-402-491-593 X 593 X 292 mm |
|
efficiency classes from F5 to F9 (EN 779 |
|
filter media: microfibre glass |
|
pleat separation by thermowelded threads |
Technical caracteristics: |
|
initial dP 75-230 Pa (as to efficiency class) |
|
final dP 600 Pa |
|
dP max. 1000 Pa |
|
temperature 80°C |
|
humidity 100% |
|
Upon request: |
|
protective grids on the air exit side |
|
high temperature resistance 100°C with peaks at 120°C |
|
|
|
|